End Caps

All dimensions are in mmDrawing depicts typical dimensionsE – as suppliedS – after free recoveryD,d – internal diameter without adhesive coatingLC – Length as per requirement

Heat shrinkable cable end caps are used to seal the ends of all type of cables and protect from ingress of water/moisture. The caps are made from thermally stabilised cross linked polymeric material. The caps are internally coated with hot melt adhesive. End caps are available with valves fitted.

SizeOrdering RefOrdering RefDia DBALCT
ESESESS
Min.Max.Min.Min.Min.%± 20%
14-4SECT 144-40144.5454015±101.2
SECT 144-60144.5656025±101.2
16-6SECT 166-45164.5504515±101.2
24-8SECT 248-45248504515±103
SECT 248-65248706520±103
36-15SECT 3615-105351611010535±104
SECT 3615-160351617016050±104
40-17SECT 4017-105401711010535±104
SECT 4017-160401717016050±104
55-25SECT 5525-105552511010535±104.2
SECT 5525-160552517016070±104.2
62-25SECT 6225-105622511010535±104.2
SECT 6225-160622517016070±104.2
75-34SECT 7534-1057534120105100±103.5
SECT 7534-1907534220190100±103.5
105-45SECT 10545-1051054512010570±103.5
SECT 10545-1601054517516070±103.5
CharacteristicValueTest Method
Physical Properties
Specific gravity1.1 ± 0.2ASTM D-1505
Water absorption1% (max)ASTM D-570 /ISO 62
Tensile strength10 N/sqmm (min)ASTM D-412 /ISO 37
Ultimate elongation300% (min)ASTM D-412 /ISO 37
Hardness45 ± 3 shore DASTM D-2240
Thermal Ageing Tests (120 °C for 500hrs)
Tensile strength8 N/sqmm (min)ASTM D-412 /ISO 37
Ultimate elongation200% (min)ASTM D-412 /ISO 37
Electrical Properties
Volume resistivity1x10¹² Ohm-cm (min)ASTM D-257 /IEC 93
Dielectric strength10kV/mm (min)ASTM D-149 /IEC 243
Dielectric constant5 (max)ASTM D-150 /IEC 250